LKQ4-125R-P PC Type Automatic Transfer Switch

PC Automatic Transfer Switch5
Quantity:
Contact Now

Product overview

The dual power automatic switch is a newly developed miniature household power switch,which is mainly used to test whether the main power supply or standby power supply is normal.When the normal power supply is abnormal, the standby power supply starts to work immediately,which ensures the continuity,rel iabi l ity and safety of power supply,This product is special ly designed for household rail installation and is specially used for Pz30 distribution box.

General

IEC60647-6(1999)/GBI14048.11-2002 “low voltage switchgear and control equipment multifunctional no.1:automatic transfer switches”

Control device:built in controller

Product structure:no power off,guide rail type,high current,small volume,two-stage type, simple structure,ATS integration

Features:fast switching speed,low failure rate,convenient maintenance and reliable perfomance

Wiring mode:front plate wiring

Conversion mode:power grid to power grid,power grid to generator,photovoltaic to urban power,automatic switching and self recovery

Product frame:125

Product current:10,16,20,25,32,40,50,63,80,100A

Product classification:direct load type

Pole No.:2,3,4

Standard:GB/T14048.11

A T S E:PC class

Switching time:0.008s/8ms

Normal operation time and installation conditions

Ambient air temperature

The maximum temperatu re shall not exceed 40°C the minimum temperature shall not be lower than -5°C,and the average temperature within 24 hours shall not be higher tehan 35 °C.

Altitude

The altitude of the installation site should not be higher than 2000m.

Atmosphenc conditions

When the maximum temperature reaches 40°C,the telative humidity of the installation site should not exceed 50%;when the temperature is the minimum tem -perature -5℃,the relative humidity is higher,for example,the temperature is 25℃, and the relative humidity is 90%.Due to the temperature change,special measures should be taken to deal with the occasional condensation on the surface of the product.

Pollution grade

The pollution grade of ATS conforms to grade 3 specified in GB/T14048.11.

Installation category

The installation type of ATS confoms to the category specified in GB/T14048.11.

Installation conditions

ATS can be installed vertically in control cabinet or distribution cabinet.Make sure the installation distance meets the requirements in Figure 8.

Model and Meaning


Technical data
Specification125A
Rated current le(A)16,20,25,32,40,50,63,80,100
Insulation voltage UiAC690V,50Hz
Rated voltage UeAC400V,50Hz
ClassificationPC class:can be manufactured withstood without short circuit current
Utilization categoryAC-33iBAC-31B
Pole No.2P3P4P
Weight(kg)1.72.12.6
Electrical life2000 times; Manual operation: 5000 times
Rated short circuit current lq50kA
Short circuit protection device(fuse)RT16-00-63A
Rated impulse withstand voltage8kV
Control circuitRated control voltage Us:AC220/50Hz Normal working conditions: 85-110%Us
Auxiliary circuit2 relays,each with two sets of contact converter contact capacity:AC200V/50Hz le=5y
Conversion time of contactor<50ms
Operation conversion time<50ms
Return conversion time<50ms
Power off time<50ms