+86-15325026862

tony@cnatse.com

LKM1 Molded Case Circuit Breaker

Molded Case Circuit Breaker2
Quantity:
Contact Now

Product overview

LKM1 series moulded case circuit breaker(herein after called circuit breaker) adopts international advanced design and manufactural technology, it can be divided into L-type (standard type), M-type (higher type)according to the rated ultimate short circuit breaking capacity (Icu). With the features of small and compact, high breaking capacity, short arcing-over distance, anti-vibration, the circuit breaker is used popularly on land and marine products, which are applied for the power distribution network of AC 50Hz,rated insulation voltage 800V (LKM1-63 to 500V), rated working voltage 690V(LKM1-63 to 400V) and below, rated current up to 1600A. It can be used to distribute electric power and protect power equipment against overload, short circuit, undervoltage etc, It also takes protective effect when motors infrequently start and protects against overload, short circuit and lacking voltage. In the series, frame ranging from 63-630A three-pole product also comes with a transparent cover, it is convenient for customers to observe the product operation.

The circuit breaker can be installed vertically, or horizontally.Standard: IEC60947-2.

Product selection

1.Blank for power distribution,2 for motor protection

2.Blank for direct operation with handle, Z for operation with rotary handle, P for

motor-driven operation.

3.There are 2 types of N-pole for 4P breaker:

A:Without current release components, N-Pole is always at making status(not

breakers);

B:Without current release components, N-Pole is made with the other three poles.

Curve

Operating conditions

1.Temperature: -5℃~+40℃; the average value within 24h shall not exceed +35℃. For the circuit breaker with thermo-magnetic

release, +40℃ is set to be the standard temperature for ratings. For temperature not between -5℃~+40℃, please contact us for temperature compensation correction;

2.Altitude: not exceed 2000m (Please contact with us for reduction coefficient if altitude at the mounted site exceed 2000m)

3.Pollution grade: Grade 3;

4.Air conditions:

At mounting site, relative humidity not exceed 50% at the max temperature of +40℃, higher relative humidity is allowable under lower temperature. For example, RH could be 90% at +20℃. Special measures should be taken when dew occurs.

Technical data

TypeLKM1-63LKM1-125LKM1-160LKM1-250LKM1-400LKM1-630LKM1-800LKM1-1250LKM1-1600
PolesP33,42,33,432,3,434,34,3, 433
Rated current InA10,16,20, 
25,32,40,
50,63
10, 16,20, 25,
32,40,50, 63,
80,100,125
100,125,
140,160
100, 125,
140 160,
180, 200,
225, 250
225,250,
315,350,
400
400,
500,
630
630,
700,
800
800,
1000,
1250
1600
Rated insulation voltage UiV500800
Rated impulsewithstand voltage UimpV60008000
Rated operation voltage UeVAC400AC400/690
Breaking capacity classLMLMLLMLMLMLMLMLM
Limit short-circuitbreaking capacity IcukA230V3550355035355050755075-----85
400V2535255035355050655065757585857585
690V--810881010201020-30-30-30
Working short-circuit breaking capacity IcskA230V1850185022225050505050-----50
400V182218251818253532.53542.5505050503650
690V--45445510510-15-15-15
Arcing distancemm50100
Operating frequencyElectrical life3000300030003000200020002000800500
mechanical life2000020000200002000010000100001000050002500

Inner accessories

Release method
and accessories code
Accessories installation
and down-leads
Accessories 
name
Electromagnetic 
release
Complex 
release
LKM1-63
LKM1-125
LKM1-16
LKM1-250
LKM1-400
LKM1-630
LKM1-800
LKM1-1250
Without parts200300
Alarm contact208308
Shunt release210310
Auxiliary contact220320
Undervoltage release230330
Shunt release,Auxiliary contact240340
Shunt release,under-voltage release250350
Secondary auxiliary contact260360
Auxiliary contact,Undervoltage release270370
Shunt release, Alarm contact218318
Auxiliary contact, Alarm contact228328
Undervoltage release, Alarm contact238338
Shunt release,Auxiliary contact, Alarm contact248348
Secondary auxiliary contact,Alarm contact268368
Auxiliary contact,Alarm contact278378
Overview

Overall and mounting dimensions(mm)

TypeOverall size (mm)Installation size (mm)
WLHW1W2L1H1H2ABΦd
LKM1-63L781357450-1569228251173.5
LKM1-63M78135825010315610028251173.5
LKM1-125L921506860-2008824301294.5
LKM1-125M92150866012220010524301294.5
LKM1-160L931517660-2009624301294.5
LKM1-250L1071658670-21511024351265
LKM1-250M1071651037014221512724351265
LKM1-400L1502571079619835716238441947
LKM1-400M1502571079619835716238441947
LKM1-630L18227111211624037016542582007
LKM1-630M18227111211624037016542582007
LKM1-800M21028011614028038516842702437
LKM1-1250M
LKM1-1600M
210406158140-610193607037511

Overall and mounting dimensions(mm)

 
ModelDimensionsUe(V)Ie(A)Mechanical life(times)Motor power(W)
ABCDE
LKM1-63251177410279K1≤0.51400014
LKM1-100301299011677K1≤0.51400014
LKM1-250351269011677K1≤0.51400014
LKM1-40044194130176115K2≤2500035
LKM1-63058200130176115K2≤2500035
LKM1-80070243130176115K2≤2500035
LKM1-125070300130176115K2≤2500035
LKM1-160070300130176115K2≤2250035