Voltage and current display relay is a microprocessor-based voltage monitoring device for single-phase AC networks to protect electrical equipment from surge voltage.The device analyzes the main voltage and displays its current value on a digital indicator.Load is switched by electromagnetic relay.The user can set the current voltage value and delay time through the button. The value is stored in non-volatile memory.Aluminum wires and copper wires can be used for connection.

Function description

When a phase of L1,L2,L3 overvoltaged,undervoltaged orphase lacked,the relay will be disconnected and automatically search for the normalphase,and switch to open the relay of the normal phase,switching priority

L1>L2>L3!

Application

Voltage and current display relay used in administrative,industrial and residential buildings and has the function of protecting single-phase lines:

●Undervoltageprotection;

●Overvoltageprotection;

●Workingundervoltmetermode;

●Overcurrent  proteciton.

Technical dataVAsVsAs
Rated supply voltageAC 220V
Operation voltage rangeAC80V-400VAC80V-350V
Rated frequency50Hz/60Hz
Overyoltage(>U)setting range230-300V
Undervoltage(140~220V
Rated current40/63A(subject to prodect label)SuLje1~40/63A
>U and0.1~30s0.5S0.5S(>Atrip delay)
Reset/start delay1~500S1~600S1~600S
Voltage measurement accuracy2%(Not exceeding 2%of the overall range)1%(Not exceeding 1%of the overall range
Rated insulation voltage400V
Dutput contact1NO
Electrical life10⁵
Mechanical life10⁶
Protection degreelp20
Pollution degree3
Altitude≤2000m
Operating temperature-50℃~55℃
Humidity≤50%at 40%(without condensation)
Storage temperature                                                -30°℃~70℃
 
 
Current specification15A25A32A50A63A
Rated operating current(In,A)1525325063
Maximum operating current Imax(A,within 10min)2530406080
Max.power of load(kW)3.65.51113.9