+86-15325026862

tony@cnatse.com

CJ19 AC Contactor

AC Contactor Series
Quantity:
Contact Now

Introduce

CJ19 contactor for capacitor switching (hereinafter called contactor) is suitable for the circuit of AC 50Hz/60Hz with rated rated voltage up to 690V. It is mainly used to add low voltage reactive power compensation equipment or cut off low voltage parallel capacitor. The contactor is equipped with a device to suppress the inrush current, which can effectively reduce the impact of the making inrush current on the capacitor and suppress the over-voltage when the capacitor is cut off.

Standard: IEC/EN 60947-4-1.

Type Designation

Operation Conditions

Ambient temperature:-5℃~+40℃, the average during 24 hours should not exceed +35℃;

Altitude:≤2000m;

Atmosphere conditions: At mounting site, relative humidity not exceed 50% at the max temperature of +40℃, higher relative humidity is allowable under lower temperature. For example, RH could be 90% at +20℃, special measures should be taken to occurrence of condensation;

Pollution degree: 3

Installation category: III

Installation conditions: the inclination between installation plane and vertical plane is within ±5°

Impact and shake: the products should locate in the places where there are no obvious impact and shake.

Technical Data

ModelCJ19-25CJ19-32CJ19-43CJ19-63CJ19-95CJ19-115
Main circuit features
Rated operating voltage(Ue)V380/400
Rated isolation voltage(Ui)V690
Rated current of controllable capacitor(In)AC-6b 400VA172936437287
Rated capacity of
controllable
capacitor(Qn)
AC-6b 230VkVar69101522.535
AC-6b 400VkVar121820304560
Rated conventional
heating current(Ith)
A2532436395115
Restrained surge capacityA ≤35In  ≤55In
Mechanical durability104  times100
Electrical durabilityAC-6b 400V  104  times1512
Operating
frequency cycles/h
AC-6b 400V   times/h300120
Coil features
Controlled power
voltage (Us)
AC50HzV110, 220, 380
Operating
voltage range
operation
voltage
V85%~110%Us when install inclination angle is +22.5°;
70%~120%Us when install inclination angle is ±5°;
release
voltage
V20%~75%Us when install inclination angle is +22.5°;
20%~65%Us when install inclination angle is ±5°;
Auxiliary contact features
Number of auxiliary contact1,221
Rated conventional heating
current(Ith)
A10
The minimum load
can be connected to
6V×10mA

Overall and Mounting Dimensions

CJ19-25, 32, 43

CJ19-25, 32, 43

 
Modeloverall dimensionsmounting dimensions
AmaxBmaxCmaxDmaxEmaxFmax
CJ19-2517645.512274.53550/60
CJ19-3218056.5132834050/60
CJ19-4318056.5132834050/60
CJ19-6319074.5154127.559100/110
CJ19-9519085.5160127.567100/110
CJ19-11519085.5160127.567100/110