+86-15325026862

tony@cnatse.com

HGL-100 Load Isolation Switch

Load Isolation Switch2
Quantity:
Contact Now

Product Details

HGL series load-isolation switch changeover Switch is applied in the circuit of AC 50 HZ,rated voltage 400V or below Rated current:16A-3150A Pole:3P,4P

Product Summary

HGL series load-isolation switch is applied in the circuit of AC 50 HZ,rated voltage 400V or below,and rated current to Max 16A~3150A. It is used to connect and break circuit by not-frequent manual operation.In addition, product with 690V is only used to electrical isolation.

Operating Conditions

1.Altitude not more than 2000m.

2.The range of ambient temperature is from 5℃ to 40℃.

3.Relative humidity not more than 95%.

4.The environment without any explosive medium.

5.The environment without any rain or snow attacking.

Note:If the product is expected to be used in the environment where temperature is over+40℃ or below -5℃ to 40℃,uses shall tell it to the manufacture.

Structure Feature

1.The switch adopts the acceleration closing mechanism in which the spring energy storage is in place and the quick instantaneous release,and the contact structure of the parallel double-breakpoint at the same time,which greatly improves the electrical performance and mechanical performance of the switch.

2.The switch conductive parts are installed in an insulating base made of glass fiber reinforced unsaturated polyester molding compound;the operation mode is :manual operation handle operation,high dielectric property,protection ability and reliable operation safety.

3.The switch has 3 poles,4poles(3 poles+adjustable neutral pole).

Operating Conditions

1.Altitude not more than 2000m.

2.The range of ambient temperature is from 5℃ to 40℃.

3.Relative humidity not more than 95%.

4.The environment without any explosive medium.

5.The environment without any rain or snow attacking.

Note:If the product is expected to be used in the environment where temperature is over+40℃ or below -5℃ to 40℃,uses shall tell it to the manufacture.

Structure Feature

1.The switch adopts the acceleration closing mechanism in which the spring energy storage is in place and the quick instantaneous release,and the contact structure of the parallel double-breakpoint at the same time,which greatly improves the electrical performance and mechanical performance of the switch.

2.The switch conductive parts are installed in an insulating base made of glass fiber reinforced unsaturated polyester molding compound;the operation mode is :manual operation handle operation,high dielectric property,protection ability and reliable operation safety.

3.The switch has 3 poles,4poles(3 poles+adjustable neutral pole).

Technical Parameter

1.The front side of the switch is provided with a marking window to indicate the on/off state of the contact;the rear observation window can be provided as needed,and the on-off state of the contact can be directly observed to ensure the reliability and safety of the switch operation.

2.The operation handle can be directly installed in switch operation(referred to as the operation inside the cabinet), or can be operated outside the cabinet door by the extension shaft(referred to as the operation outside the cabinet),providing convenient operation.

3.The normally open normally closed auxiliary contact and the installation of the dedicated backplane and the front panel rear writing can be provided as needed to meet various needs of uses.

4.When the segment is”0”,two handles can be used to lock the handle to prevent misoperation.

Model and meaning

 

Technical data

Table 1

ltemDate
Conventional thermal current (A)63A100A160A250A
Rated current In(A)40 63 80 100 125 160 200 250 
Rated insulation voltage Ui(V)(installation type IV)690 690 690 690 690 690 690 690 
Dielectric strength (V)5000 5000 5000 5000 5000 5000 5000 5000 
Rated surge-resistant voltage Uimp kV(installed category IV)6 6 6 6 6 6 6 6 
Rated working current le(A)400VAC-21B40 63 80 80 125 160 200 250 
AC-22B40 63 80 80 125 160 200 250 
AC-23B40 50 80 80 125 160 200 250 
660VAC-21B40 50 80 80 125 160 200 250 
AC-22B32 32 50 50 125 160 160 160 
AC-23B25 25 40 40 80 80 100 125 
Motor power P(KW)400V18.5 25 40 40 63 80 100 132 
660V22 22 33 33 75 75 90 110 
Rated short-time withstand current Icw(kA Rms)0.1s/1s2 2 2 2 8 8 12 12 
Rated breaking capability Icn(A Rms)AC23400V320 504 640 800 1000 1000 1600 1600 
Rated making capability Icm(ARms)AC23400V400 630 800 1000 1250 1600 2000 2500 
Rated short-current making capability Icm (kA peak value)2.84 2.84 2.84 2.84 13.6 13.6 17 17 
Mechanical durability 400V1700 1700 1700 1700 1400 1400 1400 1400 
Electrical durability 400V300 300 300 300 200 200 200 200 
Operation moment(Nm)1.2 1.2 1.2 1.2 6.5 6.5 10 10 
Table 2
ItemDate
Conventional thermal current (A)400A630A1600A3200A
Rated current In(A)315 400 500 630 1000 1250 1600 2000 2500 3200 
Rated insulation voltage Ui(V)(installation type IV)1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 
Dielectric strength (V)8000 8000 8000 8000 10000 10000 10000 10000 10000 10000 
Rated surge-resistant voltage Uimp kV(installed category IV)6 6 6 6 6 6 6 6 6 6 
Rated working current le(A)400VAC-21B315 400 500 630 1000 1250 1600 2000 2500 3200 
AC-22B315 400 500 630 1000 1250 1600 2000 2500 3200 
AC-23B315 400 500 630 
660VAC-21B315 400 400 500 1000 1000 1600 2000 2500 2500 
AC-22B315 315 315 315 800 800 800 1000 1250 1600 
AC-23B
Motor power P(kW)400V160 220 280 315 560 560 560 710 710 710 
660V185 185 185 185 475 475 475 750 750 750 
Rated short-time withstand current Icw(kA Rms)0.1s/1s25 25 25 25 50 50 50 50 50 50 
Rated breaking capability Icn(ARms)AC23400V2520 3200 4000 5040 3000 3750 4800 6000 7500 9450 
Rated making capability Icm(A Rms)AC23400V3200 4000 5000 6300 3000 3750 4800 6000 7500 9450 
Rated short-current making capability Icm (kA peak value)40 40 40 40 70 70 70 105 105 105 
Mechanical durability 400V800 800 800 800 500 500 500 300 300 300 
Electrical durability 400V200 200 200 200 100 100 100 100 100 100 
Operation moment (Nm)14.5 14.5 14.5 14.5 37 37 37 60 60 60

Operation mode

1.Direct operation: The handle is installed in the middle of the switch.

2.Operation outside the board: The handle is installed outside the door off distributing board.

Overall and mounting dimensions(mm)

Load isolation switch side operation load isolation switch of HGL-63A-100A

 
SpecificationOverall DimensionsInstallation Dimensions
ABCDabΦcd
HGL-10013 85 125 68 27 54 58 4.5 7 
14 109 125 68 27 54 58 4.5 30 

Outline and Installation Dimensions of HGL-160-1600A

 
ModelOverall DimensionsMounting DimensionsTerminal Dimensions
A  BC  D  H  a  bΦcd  eRSTYM
HGL-16013 140 135 92 36 85 120 65 5.5 27 85 20 10 3.5 25 8 
14 170 135 92 36 85 150 65 5.5 27 85 
HGL-25013 180 170 102 50 110 160 90 5.5 35 115 25 15 3.5 25 10 
14 230 170 102 50 110 210 90 5.5 35 115 
HGL-40013 230 240 135 65 160 210 140   7 50 145 32 17 5 37 10 
14 290 240 135 65 160 270 140   7 50 145 
HGL-63013 230 260 135 65 160 210 140   7 50 145 40 20 6 37 12 
14 290 260 135 65 160 270 140   7 50 145 
HGL-800/3280 285 170 80 200 255 175   9 72 180 50 20 6 48 12 
HGL-100013 378 312 170 120 200 353 175   9 72 185 60 20 8 48 12 
14 498 312 170 120 200 473 175   9 72 249 
HGL-125013 378 356 170 120 200 353 175   9 72 185 80 20 8 48 12 
/4498 356 170 120 200 473 175   9 72 249 
HGL-160013 378 356 170 120 200 353 175   9 72 185 80 20 10 49 12 
/4498 356 170 120 200 473 175   9 72 249
 

Load isolation switch side operation load isolation switch of HGL-2000A-3200A

 
SpecificationExternal Dimension and Installation Dimension
AB/B*abeR/R*T/T*Y/Y*ZIZ*
HGL-2000A/3378 306/502347 212 185 60/608/1098/8588/115
HGL-2000A4498 306/502470 212 249 60/608/1098/8588/115
HGL-2500A/3378 306/502347 212 185 80/808/1298/8588/115
HGL-2500A4498 306/502470 212 249 80/808/1298/8588/115
HGL-3200A/3378 306/502347 212 185 80/10010/1593/8388/120
HGL-3200A4498 306/502470 212 249 80/10010/1593/8388/120

Outline and Installation Dimensions of HGLC-160-1600

ModelOverall DimensionsMounting DimensionsTerminal Dimensions
ABCDEHabΦceRSTYM
HGL-160/3195 135 124 36 140 85 120 95 7 20 20 10 3.5 52 8 
14 225 135 124 36 170 85 150 95 7 20 
HGL-25013 235 170 132 50 180 110 160 115 9 20 25 15 3.5 60 10 
14 285 170 132 50 230 110 210 115 9 20 
HGL-40013 300 240 164 65 230 160 210 180 11 3532 17 5 80 10
14 360 240 164 65 290 160 270 180 11 35 
HGL-630/3300 260 164 65 230 160 210 180 11 3540 20 6 80 12 
/4360 260 164 65 290 160 270 180 11 35
HGL-100013 473 312 232 120 378 200 350 230 10 4060 20 6 98 12 
/4593 312 232 120 498 200 470 230 10 40 
HGL-125013 473 356 232 120 378 200 350 230 10 40 80 20 8 98 12 
/4593 356 232 120 498 200 470 230 10 40
HGL-160013 473 356 232 120 378 200 350 230 10 40 80 20 8 99 12 
14 593 356 232 120 498 200 470 230 10 40