+86-15325026862

tony@cnatse.com

LKW1 Frame Circuit Breaker

Frame Circuit Breaker
Quantity:
Contact Now

Introduce

LKW1 series intelligent air circuit breakers (hereinafter called ACB) are applied for the network circuit of AC 50Hz, rated voltage 400V, 690V and rated current between 630A and 6300A. Mainly used for distributing energy and protecting the circuit and power supply device against short-circuit,
undervoltage, single-phase ground fault, etc. The ACB has intelligent protection function and the key parts adopt intelligent release. The release canmake the accurate selective protection, which can avoid cutting off the power and improve the reliability of power supply. The products conform with IEC60947-1,IEC60947-2 standards.

Type designation

1.Rated current in scope of frame current

2000 Type-in: 630A, 800A, 1000A, 1250A, 1600A, 2000A;

3200 Type-in: 2000A, 2500A, 3200A;

6300 Type-in: 4000A, 5000A, 6300A;

2.Pole number

3-default, 4-4 pole

3.Installation

Fixed type-horizontal, vertical

Draw out type-horizonal, vertical

Note: 2000 type have vertical wiring, others are horizontal wiring

4.Control unit

L type-dial switch mode, over-current protection (overload, short delay,

instantaneous).

2M type-digitaldisplay,over-current protection (overload, shortdelay,

instantaneous), 4P or 3P+N have earthing protection (3M type is LCD display).

2H type-communication function, digital display, over-current protection

(overload, short delay, instantaneous), 4P or 3P+N have earthing protection (3H

type is LCD display).

5.Common use accessory

Closing electromagnet-AC230V, AC400V, DC220V

Undervoltage release-AC230V, AC400V, undervoltage instantaneous,

undervoltage time-delay

Release (close) magnetic iron-AC230V, AC400V, DC220V

Electric operation mechanism-AC230V, AC400V, DC110V, DC220V

Auxiliary contact-standard type (4a4b), special type (5a5b, 6a6b)

Note: a-normal open, b-normal close

6.Optional accessory

Mechanical inter-lock:

one circuit breaker (1lock+1key)

two circuit breaker (steel cable inter-lock, connecting rod inter-lock, 2lock+1key)

three circuit breakers (3locks+2keys, connecting rod inter lock)

Automatic power transfer system

Current transformer connected with neutral lead

Operation Conditions

Operating conditions
ItemDescription
Ambient temperature-5℃~+40℃ (except special order products)
Altitude≤2000m
Pollution grade3
Safety categoryMain circuit and undervoltage tripping coil is IV, other auxiliary and control circuit is III
Installation positionVertical installed, tilt not exceed 5 degree
Environmental protectionMost of parts use recyclable and degradable materials
Isolating functionWith isolating function

Specifications

Curves

 
Data
TypeLKW1-2000LKW1-3200LKW1-6300
Pole3P, 4P3P, 4P3P, 4P
Using categoryBBB
Rated current InA630, 800, 1000,1250, 1600, 20002000, 2500, 32004000, 5000, 6300
Rated frequencyHz505050
Rated operation voltage UeV400, 690400, 690400, 690
Rated insulation voltage UiV800800800
Arcing distancemm000
Rated impulse withstanding voltage UimpV800080008000
Rated operation short circuit   breaking capacity Ics (O-t-CO)400VkA5080100
660VkA405075
Rated limiting short circuit400VkA8080120
breaking capacity Icu (O-t-CO)660VkA506585
Rated short time withstanding current Icw (O-t-CO, AC400V 0.4S)400VkA506585
Operation lifePer hourtimes202010
Electricaltimes1000500500
Mechanicaltimes1000050005000
Full breaking timems20~3020~3020~30
Full closing timems55~7055~7055~70
Power consumption3PW36012002000
4PW45017502300
Resistance of each poleFixed typeμΩ119-
Draw out typeμΩ201410
Dimensions (L ×W × H)3P fixed typemm362 ×323 ×402422 ×323 ×402
3P draw out typemm375 ×461 ×452435 ×471 ×452
4P fixed typemm457 ×323 ×402537 ×323 ×402
4P draw out typemm470 ×461 ×452550 ×471 ×452
Approximate weight3P fixed typekg4155
3P draw out typekg7195245
4P fixed typekg51.565-
4P draw out typekg86
 
Overload protection data
Overload protectionLKW1-2000~6300
Adjust scope Ir1(0.4-1)In (pole difference 2%)
1.05 Ir1h2h non-tripping
1.3 Ir1h≤1h tripping
1.5 Ir1s153060120240480
2.0 Ir1s8.416.933.767.5135270
Accuracy%±15
 
 
Short circuit, short time delay
Adjust scope Ir1 Ir2(0.4-15)In (pole difference 2%)
Delay time tr2ms100, 200, 300, 400
Accuracy%±15
 
 
Short circuit, instantaneous
LKW1-2000LKW1-3200LKW1-6300
Adjust scope Ir1 Ir31In-50kA1In-75kA1In-100kA
Accuracy%±15±15±15
 
 
Load monitoring outputLKW1-2000~6300
Load adjust scope Ic1(0.2-1)In (pole difference 2%)
Delay time tc1tr1 ×0.5
Load adjust scope Ic2(0.2-1)In (pole difference 2%)
Delay time tc2tr1 ×0.25 (anti-time limit)
Accuracys60 (set time limit)
%±10

Overall and mounting dimensions

Installation and figure dimension of LKW1-2000A fixed type circuit breaker

Installation and figure dimension of LKW1-3200A fixed type circuit breaker

Installation and figure dimension of LKW1-4000A fixed type circuit breaker

Installation and figure dimension of LKW1-6300A fixed type circuit breaker

Installation and figure dimension of LKW1-2000A draw-out type circuit breaker

Installation and figure dimension of LKW1-3200A draw-out type circuit breaker

Installation and figure dimension of LKW1-4000A draw-out type circuit breaker

Installation and figure dimension of LKW1-4000A(4P) draw-out type circuit breaker

Installation and figure dimension of LKW1-6300A draw-out type circuit breaker

Installation and figure dimension of draw-out type circuit breaker (Inm=3200A 3P 4P)

Dimension of panel hole see picture and table Unit:mm

Interlock device of circuit breaker see picture Unit:mm

Interlock device of vertical install circuit breaker

Characteristic of intelligent controller

Basic function
Overload longtime-delay/anti-time limit protection
Short circuit short time-delay/anti-time limit protection
Short circuit short time-delay timing protection
Short circuit instantaneous protection
Insulate earth fault protection
 
Testing function
Panel keyTrippingTest the time current characteristic of    release and situation of operation device
Remote monitoring functionNon-trippingTest the time current characteristic of release
Remote monitoring code signal optocouplerRelay (contain power) moduleOutput of various working condittion
Communication function
Communicate typeRS485(communication) I/OUser should consult with the manufacturer
 
Under-voltage releaseRated working voltage Ue(V)AC400  AC230
Acting voltage (V)(0.35~0.7) Ue
Reliable close voltage (V)(0.85~1.1) Ue
Non close voltage (V)≤0.335Ue
Power loss12VA (WFW1-1000 5VA)
 
Shunt releaseRated control power voltage Us(V)AC400  AC230  DC220  DC110
Acting voltage (V)(0.7~1.1) Ue
Power loss40VA 40W (WFW1-1000 5VA)
Open timeless than 30ms
 
Close electromagnetic ironRated control power voltage Us(V)AC400  AC230  DC220  DC110
Acting voltage (V)(0.85~1.1) Ue
Power loss40VA 40W (WFW1-1000 5VA)
Open timeless than 70ms
 
Motor operating deviceRated control power voltage Us(V)AC400  AC230  DC220  DC110
Acting voltage (V)(0.85~1.1) Ue
Power loss40VA 40W (WFW1-1000 5VA)
Open timeless than 5s